The power counter Victron ET112 (Rel300100000) It is a meter single-phase of direct measurement up to 100 a, manufactured by Carlo Gavazzi according to the specifications of Victron, which is integrated with the GX devices and the system ESS of Victron. Its main function is to act as network counter: It measures imported and exported energy in real time so that the system regulates self-consumption, battery charge and pouring limitation. Can also measure the output inverter Fv, a AC or concrete AC charges. Offers Class 1 accuracy in active energy according to EN 62053-21 and an accuracy of ± 0.5% reading in current and tension, with a Update rate of 750 ms. Is mounted in DIN rail and communicates by RS485 (Modbus), by direct cable, the interface Victron RS485 to USB or wireless converters ZigBee. Your data is displayed on the GX device and in the Portal VRM.
Detailed technical characteristics
- Reference Victron: Rel300100000
- Model Carlo Gavazzi: Et112-din.av01.x.s1.x
- Number of phases: 1
- Nominal maximum current: 100 a
- Type of measurement: Direct (Direct / Shunt)
- Base current (IN) / minimum (IMIN): 5 A / 0.25 A
- Start current: 40 mA
- Active energy precision: Class 1 according to EN 62053-21
- Precision reactive energy: class 2
- Current precision and tension: ± 0.5% reading
- Communication: RS485 (Modbus)
- Update rate: 750 ms
- Screen: not (Communication indication LED)
- Assembly: DIN rail
- Energy Registration: arithmetic
- Compatibility: GX devices Victron with Venus OS, Portal VRM
- Connection to the GX: RS485 cable, RS485 interface to USB or converters ZigBee
- Applications: Network Counter ESS, Measurement of inverter FV, AC generator or AC loads
- System manufacturer: Victron Energy, with quality system ISO 9001: 2015 (TÜV NORD, valid up to 2027)
Benefits of the Energy Counter Victron Et112
The brain of measuring an ESS single-phase
In a system Ess Victron, the inverter-Farger needs to know at every moment if the house is importing or exporting energy. The ET112, installed at the connection point with the network, sends that information to the GX device, which adjusts the loading and unloading of the lithium batteries and solar production to maximize self-consumption and, if necessary, apply zero.
100 A of Direct Measurement
When measuring directly until 100 a, the ET112 covers the vast majority of supplies single-phase Residential and commercial without the need for current transformers, which simplifies the installation in the box.
Class 1 precision
With Class 1 in active energy (EN 62053-21) and ± 0.5% In current and tension, the system makes its decisions on reliable data, something essential for self-consumption control.
Quick answer: 750 ms
The update rate of 750 ms It allows the system to react with agility to consumption changes, such as the start of an appliance, reducing the energy that is imported or exported without wanting.
Versatile: Network, FV, Generator or Loads
In addition to a network counter, the ET112 can measure the output of a inverter FV connected to network, a generator or a specific load, and show those data in the GX and VRM.
Installation and election of the counter
ET112 or ET340?
For one Monophasic connection to the network, Victron Recommend a counter single-phase Like the ET112. For a connection three-phase, or for a inverter Fv three-phase, a counter should be used three-phase like Et340. In a single-phase installation with a inverter FV that must also be measured, can be used Two Et112 or an ET340.
If you overcome 100 to
If the current of the installation exceeds the 100 a, Victron recommends using an accountant with Current transformers.
Connection to the GX device
The most usual way is the interface Victron RS485 to USB, Available at 1.8 and 5 m. If it is not possible to tend cable, there are wireless converters ZigBee. Remember that many inverters solar They offer direct reading in the system Victron And they do not need accountant to measure their production.
Complete your system with inverters hybrid, solar panels and Solar kits on Tienda Solar, and consult in the Blog Tienda Solar Our technical guides developed by experts.
Frequently Asked Questions (FAQ)
1. What is the accountant for Victron Et112?
Mainly as network counter in systems ESS single-phase of Victron, to measure imported and exported energy. Can also measure a inverter Fv, a generator or AC loads.
2. What maximum current does it admits?
Until 100 a in direct measurement in an installation single-phase. For superior currents, a counter with current transformers is required.
3. Do you have screen?
No. ET112 has no screen; Your data is consulted in the GX device and on the portal VRM. It has an LED indicating communication activity.
4. How do you connect to the GX CERBO?
For Rs485, usually through the interface Victron RS485 to USBor wirelessly with converters ZigBee of Victron.
5. Can I use it in a three-phase installation?
Network Counter three-phase. To measure a three-phase connection, Victron Indicate using a counter three-phase like Et340.
6. What precision does it have?
Class 1 in active energy according to EN 62053-21, class 2 in reactive energy and ± 0.5% Reading in current and tension.