The Stationary Battery Tab 18 OPzS 2250 it's a glass OPzS of 2v with a nominal capacity of 2,250 ah according to the denomination and the first model of the range with eight poles, designed for storage banks of very large capacity in industry, data centers, telecommunications, substations and isolated micro-grinds. Their 18 Tubular positive plates alloy Bajo Antimony (≤1.65% SB) delivered 3,038 Ah in C24, 3.780 Ah in C120 and 3.917 Ah in C240, in addition to 2.811 Ah in C12. The Internal resistance of 0.140 MΩ and the Short circuit current of 14,450 A They ensure a very stable bank tension with high-power loads and equipment. With 786 mm tall with connectors, it maintains the same height as the vessels of six poles, which facilitates combining banks in the same room. Offers 2,300 cycles 60% of DOD and one 20 year design life in flotation at 20 ° C, and it meets IEC 61427, IEC 60896-11, DIN 40736-1 and EN 50272-2.
Detailed technical characteristics
Electrical data
- Model: TAB 18 OPzS 2250
- Technology: OPzS, lead-open acid with positive tubular plate
- Nominal voltage: 2V
- Nominal capacity (denomination DIN, C10:) 2,250 Ah
- CP240 capability (1.85 V / element, 20 ° C:) 3,917 Ah
- Capacity C120 (1.85 V / element, 20 ° C:) 3,780 Ah
- Capacity C48 (1.80 V / element, 20 ° C:) 3.419 Ah
- Capacity C24 (1.80 V / element, 20 ° C:) 3,038 Ah
- CP12 capacity (1.80 V / element, 20 ° C:) 2.811 Ah
- Internal resistance: 0,140 mΩ
- Short circuit current: 14,450
- Positive plates: 18
- Number of poles: 8
Mechanical data
- Long: 487 mm
- Width: 212 mm
- High no connectors: 772 mm
- High with installed connectors and covers: 786 mm
- Distance between poles: 110 mm
- Weight with electrolyte (approx.:) 184 kg
- Dry weight (approx.:) 125 kg
Construction
- Positive plates: tube with special alloy bajo Antimony (≤1.65% SB)
- Negative plates: gridboat with optimized low antimony alloy
- Separators: Low resistance microporous PVC
- Electrolyte: diluted sulfuric acid
- Container: Transparent san high resistance to impact
- Cover: ABS robust
- Poles: brass insert M10 with rubber gasket, acid resistant and suitable for impedance measurement
- Connectors: screwed, encapsulated head steel screws; flexible isolated series and rigid optional
- Plugs: antideflages ceramics, also available in funnel version
Operation
- Cycles: 2.300 to 60% of DOD, 20 ° C
- Design life: 20 years in Standby, 20 ° C
- Recommended temperature: 10 ° C at 30 ° C
- Maximum temperature: 55 ° C
- Self: approx. 2.5% monthly at 20 ° C
- Maximum storage: 3 months at 20 ° C, , 2 months at 30 ° C or 1 month at 40 ° C
- Maintenance: low need of filling
Standards and Quality
- IEC 61427: batteries for photovoltaic systems
- IEC 60896-11: open-acid stationary batteries
- DIN 40736-1: elements OPzS
- EN 50272-2: stationary battery security
- European manufacturing with ISO 9001, , ISO 14001 and BS OHSAS 18001
Benefits of the stationary battery Tab 18 OPzS 2250
The 18th OPzS 2250 opens the format of eight poles of Tab: a casing 487 x 212 mm host 18 tubular positive plates and distributes the current between four pairs of terminals. This format leap is reflected directly in the benefits with respect to 16 OPzS 2000: the C120 goes from 2,972 to 3,780 ah, the C12 2.279 to 2,811 ah and the low internal resistance of 0,160 to 0.140 MΩ.
More than 3,000 AH in 24 hours
Is the first glass of the Tab range that exceeds 3,000 Ah at 24-hour download (3,038 Ah in C24). This data is decisive in supporting systems that must guarantee a full day of autonomy, as data centers, hospitals, telecommunications nodes or electrical substations, and allows you to cover those needs with a single serial string.
Same height as the six-pole glasses
With 772 mm tall786 mm with connectors), the 18 OPzS 2250 coincides in height with 14 OPzS 1750, the 15 OPzS 1875 and 16 OPzS 2000. For engineering, this simplifies the design of rooms with several banks of different capacity: benches, wiring tours and work height are kept homogeneous.
Industrial scale power delivery
The internal resistance of 0.140 MΩ and the short circuit current of 14,450 A they allow feeding systems with several inverters hybrid three-phase, telecommunications or large motors with a minimum voltage drop, improving global efficiency and system stability.
Tubular plate for decades of service
The tubular positive plate retains active matter during cycling, unlike flat plate batteries such as aGM batteries. Tab certifies 2,300 cycles 60% of DOD and 20 years of design life, essential figures to amortize an investment of this scale.
Design of very large capacity benches
Energy and weight estimated
Own guidance calculation on nominal capacity (it is not a manufacturer's data:)
- By glass: some 4.5 kWh in C10 and some 7.5 kWh in C120
- 24V Bank (12 glasses:) some 54 kWh nominal in C10 and some 2.208 kg electrolyte
- 48V Bank (24 glasses:) some 108 kWh nominal in C10 and some 4,416 kg electrolyte
Installation, Connection and Protections
With 184 kg by glass and 487 mm long, the installation requires mechanical lifting means, benches dimensioned for the total load and a study of the soil carrying capacity. Each union between eight poles vessels is normally performed with four connectors, with a distance between 110 mm poles. The short circuit current of 14,450 A determines the necessary cutting power in fuses and continuous disconnectors.
Loading and generation
The charger, rectifier or inverter solar you must admit lead-acid batteries open and configure with the tensions of the TAB manual, which are not listed on the Technical Sheet. In large-scale isolated photovoltaic systems, the bank is combined with a wide field of solar panels upon structures for solar panels of soil, and for more reduced projects solar kits they are a good base.
For daily cycling applications connected to the network, you can also assess our batteries Peakshaving or the lithium batteries. On Tienda Solar we advise you on storage projects of any size, and in the Blog Tienda Solar you will find purchase guides and technical items prepared by experts.
Frequently Asked Questions (FAQ)
1. What changes when moving from six to eight poles?
With eight poles (four positive and four negative), the glass of the glass is distributed between four roads in parallel, which reduces the intensity by terminal and by connector and limits the heating of the connections. This format is the one that allows Tab to stay 18 positive plates and reach capabilities up to 3.917 Ah in C240 in a single glass.
2. Is it suitable for a 24-hour backup system?
Yes. With 3,038 Ah in C24 at 20 ° C up to 1.80 V per element, a vessel string 18 OPzS 2250 can supply, as a guiding calculation, an average current of some 127 A for 24 hours. It is a very suitable capacity for data centers, hospitals or telecommunications nodes that require a full day of autonomy.
3. What length does a bank of 110V occupy?
A 110V system requires, as arithmetic reference, some 55 glasses in series Only the sum of its lengths (487 mm by glass) round 26.8 m, without counting the separation between elements. That's why these banks usually distribute in various rows or stepped benches, what should be foreseen from the design of the room.
4. Can I use it for self-consumption connected to network with daily cycling?
It is technically possible with a hybrid inverter compatible lead-acid batteries open, but for intense daily cycling applications connected to the network, they usually prove more practical lithium batteries o Specific Peakshaving solutions, for its highest depth of useful download and absence of maintenance. The OPzS as the 18th OPzS 2250 stand out in isolated facilities and backup systems.
5. What requirements should the battery room meet?
In addition to the ventilation calculated according to EN 50272-2, the room must have acid-resistant floor, benches suitable for weight, restricted and signposted access, absence of sources of sparks or flames and, preferably, a controlled temperature between 10 ° C and 30 ° C. It is also advisable to have means for eyewash in case of contact with the electrolyte.
6. What is the difference with 20 OPzS 2500?
Both share the format of eight poles and the casing 487 x 212 x 772 mm. The 20th OPzS 2500 incorporates two more positive plaques, reaching 4,076 Ah in C120 facing the 3,780 Ah of 18 OPzS 2250, with a weight of 201 kg versus 184 kg. The choice depends on the ability of the Bank.