• New
Stationary Battery Tab 1200AH 2V 12 OPzS 1200
Stationary Battery Tab 1200AH 2V 12 OPzS 1200

Stationary Battery Tab 1200AH 2V 12 OPzS 1200

12OPzS1200TB
€563.30
Tax included

The Stationary Battery Tab 12 OPzS 1200 is the glass OPzS of 2v greater capacity within the series 646 mm high from the manufacturer, with a nominal capacity of 1,200 Ah according to the DIN Denomination and four poles. Thanks to his 12 tubular positive plates alloy Bajo Antimony (≤1.65% SB), rub the 2,000 Ah in slow downloads (1,908 Ah in C120 and 1,985 Ah in C240) and delivery 1.391 Ah in C12, figures designed for large isolated solar installations, rural microred, telecommunications and industrial backing. Your internal resistance of 0.228 MΩ and the Short circuit current of 8,850 A guarantee a stable bank tension with inverters of very high power. Maintains the durability of tubular technology, with 2,300 cycles 60% of DOD and one 20 year design life In flotation at 20 ° C. Meets IEC 61427, IEC 60896-11, DIN 40736-1 and EN 50272-2, with European manufacturing ISO 9001 and ISO 14001.

 

Detailed technical characteristics

Electrical performance

  • Model: TAB 12 OPzS 1200
  • Technology: OPzS, lead-open acid with positive tubular plate
  • Nominal voltage: 2V
  • Nominal capacity (denomination DIN, C10:) 1,200 Ah
  • CP240 capability (1.85 V / element, 20 ° C:) 1,985 Ah
  • Capacity C120 (1.85 V / element, 20 ° C:) 1,908 Ah
  • Capacity C48 (1.80 V / element, 20 ° C:) 1,695 Ah
  • Capacity C24 (1.80 V / element, 20 ° C:) 1.487 Ah
  • CP12 capacity (1.80 V / element, 20 ° C:) 1.391 Ah
  • Internal resistance: 0,228 mΩ
  • Short circuit current: 8.850
  • Positive plates: 12
  • Number of poles: 4

Dimensions and weight

  • Long: 275 mm
  • Width: 210 mm
  • High no connectors: 646 mm
  • High with installed connectors and covers: 660 mm
  • Distance between poles: 140 mm
  • Weight with electrolyte (approx.:) 91 kg
  • Dry weight (approx.:) 66 kg

Internal and material design

  • Positive plates: tube of special alloy with bajo Antimony (≤1.65% SB)
  • Negative plates: gridboat with optimized low antimony alloy
  • Separators: Low resistance microporous PVC
  • Electrolyte: diluted sulfuric acid
  • Container: Transparent san high resistance to impact
  • Cover: ABS robust
  • Poles: brass insert M10 and rubber gasket, acid resistant and suitable for impedance measurement
  • Connectors: screwed, encapsulated head steel screws; flexible isolated series and rigid optional
  • Plugs: antideflages ceramics, also available in funnel version

Benefits

  • Cycles: 2.300 to 60% of DOD, 20 ° C
  • Design life: 20 years in Standby, 20 ° C
  • Recommended temperature: 10 ° C at 30 ° C
  • Maximum temperature: 55 ° C
  • Self: approx. 2.5% per month at 20 ° C
  • Maximum storage: 3 months at 20 ° C, , 2 months at 30 ° C or 1 month at 40 ° C
  • Maintenance: low need of filling

Certifications

  • IEC 61427: batteries for photovoltaic systems
  • IEC 60896-11: standard lead-acid batteries open
  • DIN 40736-1: elements OPzS
  • EN 50272-2: stationary battery security
  • European manufacturing with ISO 9001, , ISO 14001 and BS OHSAS 18001

Benefits of the stationary battery Tab 12 OPzS 1200

The 12 OPzS 1200 occupies a strategic position in the Tab range: it is the maximum available capacity without exceeding 660 mm tall with connectors. For projects with wardrobe, shelves or low ceiling rooms, this allows to reach capabilities close to the 2,000 Ah in C120 without going to the glasses of 797 mm of the upper series.

A two plaque jump compared to 10 OPzS 1000

In front of the 10 OPzS 1000, this glass incorporates two positive plaques more and a longer casing (275 mm facing 233 mm). The result is an increase of 200 Nominal ah, a C120 that passes from 1,592 to 1,908 ah and an internal resistance that falls down 0.261 to 0.228 MΩ. Is the logical reference when a bank of 10 OPzS 1000 falls short and you want to avoid the assembly of strings in parallel.

Power for systems three-phase and microred

With 0,228 mΩ of internal resistance and 8.850 short circuit current, the bank responds with solvency to systems formed by several inverters hybrid or inverters-brakes in three-phase configuration, usual in agricultural holdings, small industries or rural micro-grinds that group several consumption.

Long life with tubular technology

The tubular positive plate protects active matter from daily cycling wear, something that flat plate batteries, such as aGM batteries, they can not match in demanding applications. Tab certifies 2,300 cycles 60% of DOD and 20 years of design life, and their curves confirm that with more moderate downloads life in cycles increases significantly.

Planning a bank with Tab 12 OPzS 1200

Energy and weight estimated

Own guidance calculation on nominal capacity (it is not a manufacturer's data:)

  • By glass: some 2.4 kWh in C10 and some 3.8 kWh in C120
  • 24V Bank (12 glasses:) some 28.8 kWh nominal in C10 and some 1,092 kg electrolyte
  • 48V Bank (24 glasses:) some 57.6 kWh nominal in C10 and some 2,184 kg electrolyte

Specific connection

This model has a distance between 140 mm poles, different from the 110 mm of 9 OPzS 900 and 10 OPzS 1000, so it requires the connectors corresponding to its format. The short circuit current of 8,850 A it should be considered when dimensioning fuses and continuous disconnectors, and the battery room must comply with the standard EN 50272-2.

Load and photovoltaic generation

The bank must be managed with a inverter solar or regulator compatible with lead-acid batteries open, adjusted according to the TAB manual, since the technical sheet does not indicate the load voltages. To recharge an accumulator of this capacity you need a large photovoltaic generator: combine it with solar panels high-power structures for solar panels of soil, or consult our solar kits for isolated installations.

If your project prioritizes the minimum maintenance, you can also compare this solution with ours lithium batteries. On Tienda Solar you will find everything you need for isolated large-scale installations, and in the Blog Tienda Solar you have purchase guides and technical items prepared by experts.

Frequently Asked Questions (FAQ)

1. What is the difference between Tab 12 OPzS 1200 and 12 OPzS 1500?

Both have 12 positive plates, the same plant (275 x 210 mmand the same distance between poles (140 mm). The difference is in the height: the 12 OPzS 1200 measures 646 mm (660 mm with connectors) and the 12 OPzS 1500 reaches 797 mm. The highest plates of the latter give you more capacity (2.226 Ah in C120 facing 1,908 ah), in exchange for more height and weight. If the vertical space is limited, the 12 OPzS 1200 is the right option.

2. Can I use the connectors of the 10 OPzS 1000?

No. The 12 OPzS 1200 has a distance between 140 mm poles, while the 9 OPzS 900 and 10 OPzS 1000 they have 110 mm. Therefore, the connectors between vessels must be the specific ones of this format.

3. Why are capabilities measured up to 1.80 V and others up to 1.85 v per item?

The final discharge voltage it depends on the regime. In downloads from 12 to 48 hours (C12, C24 and C48), Tab measures capacity until 1.80 V per element, while in very slow downloads of 120 and 240 hours (C120 and C240) the reference is 1.85 V per element. It is important to use the capacity corresponding to the actual regime of the installation when dimensioning the bank.

4. What surface does a 48V bank occupy?

A 48V bank requires 24 glasses of 275 x 210 mm each one. As a guidance calculation, the sum of its plants round the 1.4 m², to which you have to add the separation between vessels, the connectors and the access corridors for maintenance. Stepped or several-level benches allow reducing the total area.

5. What safety precautions have to be taken when manipulating the vessels?

When working with open-acid-acid batteries should be used protective goggles, acid resistant gloves and isolated tools, remove metallic objects such as rings or watches and do not smoke or generate sparks in the room. The encapsulated head screws and the antideflagers ceramic plugs of Tab reduces risks, but they do not replace these measures.

6. Is it suitable for a microrred or a system three-phase isolated?

Yes. Your ability to 1,908 Ah in C120 by glass and its low internal resistance of 0.228 MΩ they allow feeding systems with several inverters in three-phase configuration, provided that all equipment admits lead-acid batteries open and are configured with the same load parameters.